Numerical Simulation and Damage Assessment of Substation Involving Dynamic Interaction

WEN Bo, ZHANG Lu, NIU Ditao, YANG Dangchao

Abstract

The seismic performance and failure mechanisms of the substation structure system considering dynamic interaction on the main structure and substructure was studied systematically, based on the mechanism of primary-secondary structure dynamic interaction, implicit dynamics numerical simulation analysis and shaking table test. Seismic response of the structure system was analyzed in some aspects such as internal force, displacement and acceleration. This paper obtained the interaction mechanism between the electrical equipment with main structure, the dynamic magnification factor of the electrical equipment and the dynamic property values, and put forward the seismic performance goals of the main structure. Meanwhile, the results based on the displacement revised factor method established the level damage assessment model and the overall damage assessment model, and then proved the correctness of the damage assessment model by shaking table test. These research results have important reference function on seismic design and seismic damage assessment of the similar lifeline engineering and industrial architectures with complex equipment.

 

Keywords: substation structure system,  dynamic interaction,  numerical simulation,  shaking table tests,  damage assessment model


Full Text:

PDF


References


LI J, CHEN H, SUN Z S. Shaking table tests on spatial structure -equipment model systems [J]. Engineering Mechanics,2003. 20( 1): 157-161. (In Chinese)

WEN B. NIU В T. Seismic vulnerability analysis for the main building of the large substation [J], China Civil Engineering Journal, 2013. 46(2):19-23.(In Chinese)

WEN B, TACIROGLU E, NIU В T. Shake table testing and numerical analysis of transformer substations including main plant and electrical equipment interaction [J]. Advances in Structural Engineering. 2015.18( 11): 1959-1980.

WEN B. XU H X. HOU C X. Analysis on the dynamic characteristics of equipment-structure interaction for the main building of a transformer substation[J]. Journal of Xian University of Architecture & Technology,2012,44(5):620-625.(In Chinese)

PARK Y J. ANG A. Mechanistic seismic damage model for reinforced concrete [J]. Journal of Structural Engineering, 1985. Ill (4):740-756.

HINDI R A. SEXSMITH R G. A proposed damage model for RC bridge columns under cyclic loading [J]. Engineering Spectra, 2001.17( 2 ):261-290.

GUO Z M. ZHANG Y T. FAN J. et al. Damage model of RC members based on stiffness degradation am! fiber-brain elements J .Journal of Hunan Univeisity (Natural Sciences),2017,44(3): 76-87.(In Chinese)

NIU D T. HEN I. J. A modified seismic damage model with double variables for reinforced concrete structures [J], Earthquake Engineering and Engineering Vibration, 1996.16(4): 44-54. (In Chinese)

ILIZ X, CHEN Y, LI N. A damage model for reinforced concrete members based on material damage [J]. Engineering Mechanics, 2014. 31(6):53-59. (In Chinese)

ZHANG Y T. DU X J. YANG L. Research on seismic performance assessment based on component damage for RC frame structure [j_. Journal of Hunan University(Natural Sciences), 2016. 43(5 );9-21. (In Chinese)

CAO M. Shaking table test of large substation considering the interaction of structure and electric equipment [D] Xian: College of Civil Engineering, Xian University of Architecture and Technology, 2014:10-19. (In Chinese)

CHEN F J. VI W J. Incremental dynamic analysis of corroded reinforced concrete bridge columns subjected to near-filed earth-quake [J]. Journal of Hunan University (Natural Sciences), 2015,42(3):!8. (In Chinese)